Flush mounting gas leak detectors for methane and LPG for civil environments
-
DESCRIPTION
General features0
Sicurgas is a device that, through a sensitive sensor, detects methane gas concentration (P71) and LPG concentration (P72) in civil environments.
- Shockproof insulating material casing.
- Semiconductor sensor for gas detection.
- Sicurgas has three warning lights: green LED – indicates that the detector works properly, yellow LED – indicates detector failure, red LED – indicates the gas presence in the environment (ALARM).
- The used relay is sealed and filled with inert gas, which ensures in any case the absolute absence of sparks during switching phases.
Electric features- Power supply: 230Vac – 50Hz.
- Consumption: 3 VA.
- Output through electromagnetic relays.
- Contacts rating: 5(3)A – 250Vac.
-
ADVANTAGES
0
Sicurgas is a device that, through a sensitive sensor, detects methane gas concentration (P71) and LPG concentration (P72) in civil environments.
Advantages -
TECHNICAL SPECIFICATION
CODE GAS TYPE COLOR POWER SUPPLY CONTACT RATING TEST BUTTON OPERATING TEMPERATURE PROTECTION DEGREE P71 Methane Anthracite 230Vac - 50Hz 5(3)A - 250Vac Yes - pull cord 0 ÷ 40 °C IP42 P71B Methane White 230Vac - 50Hz 5(3)A - 250Vac Yes - pull cord 0 ÷ 40 °C IP42 P71C Methane Silver 230Vac - 50Hz 5(3)A - 250Vac Yes - pull cord 0 ÷ 40 °C IP42 P72 LPG Anthracite 230Vac - 50Hz 5(3)A - 250Vac Yes - button 0 ÷ 40 °C IP42 -
HOMOLOGATION AND INSTALLATION
Homologation
- Complies with EN 60730-1 standards
Installation and use- Flush mounting in 3-module 503 embedded boxes by means of 2 screws (supplied).
COMPATIBLE PLATES
- BTICINO Axolute, Livinglight, Light, Light tech
- Living VIMAR Idea, Rondò, Plana, EikoN
- GEWISS Playbus e Playbus Young
- AVE Banquise, Ave Yes
- LEGRAND Cross.
- Sicurgas operates when the gas concentration in the air is much under the lower explosion limit (L.E.L.), immediately turning on the red light.
- In case of alarm, interferes as well an acoustic alarm that is going to prevent the danger. Simultaneously Sicurgas is making the relay to interfere in order to control the gas interception valve.
- Sicurgas has three warning lights: green LED – indicates that the detector works properly, yellow LED – indicates detector failure, red LED – indicates the gas presence in the environment (ALARM).
- The detector controls, through a relay, the normally closed (NC) and normally open (NO) valves with manual reset.
- Sicurgas sensor, as all available on the market sensors, while being very selective can also participate for other substances, for
example: alcohol vapors, wine etc. - For example, during the use of wine while preparing food is possible, that the detector will enter in alarm situation. To avoid this
inconvenience, Sicurgas is equipped with an alarm silencing key (P61AE excluded), operated with:
– pull cord for Sicurgas P71 for methane gas (mounted up on the wall, 30 cm from ceiling);
– key under Sicurgas P72 body for LPG (mounted down on the wall, 30 cm from the floor).