Self-adjusting heating cables to maintain the temperature of fluids
-
DESCRIPTION
General features0
Suitable for maintaining the temperature of liquids inside pipes.
Power delivered ~20, ~30, ~40 W/m at 10°C.
Optimisation of energy consumption thanks to the self-adjusting feature of the cable.
- Cable composition:
– 1.25 mm² conductors
– Self-adjusting conductive core
– Polyolefin insulating sheath
– Braided copper sheath
– Outer sheath in modified polyolefin - Minimum installation room temperature -35 °C
- Maximum room temperature powered 65 °C
- Maximum room temperature not powered 80 °C
- Minimum storage room temperature -20 ÷ -25°C
- Cable dimensions
– 12.6 x 4.8 mm series K20A
– 14.6 x 4.8 mm series K30A-K40A
Electric features- Power supply 230V-50Hz
- Tolerance -0/+5 W
- Power delivered
– K20A 20 W/m at 10°C
– K30A 30 W/m at 10°C
– K40A 40 W/m at 10°C
- Cable composition:
-
ADVANTAGES
0
Suitable for maintaining the temperature of liquids inside pipes.
Power delivered ~20, ~30, ~40 W/m at 10°C.
Optimisation of energy consumption thanks to the self-adjusting feature of the cable.
Advantages -
TECHNICAL SPECIFICATION
CODE CABLE LENGTH POWER AT 10°C MAXIMUM ROOM TEMPERATURE POWERED MAXIMUM ROOM TEMPERATURE NOT POWERED MAXIMUM LENGTH OF THE HEATING CIRCUIT FROM THE SUPPLY POINT K20A25 25 m 20 W/m 65 °C 80 °C 170 m K20A50 50 m 20 W/m 65 °C 80 °C 170 m K20A100 100 m 20 W/m 65 °C 80 °C 170 m K20A500 500 m 20 W/m 65 °C 80 °C 170 m K30A25 25 m 30 W/m 65 °C 80 °C 140 m K30A50 50 m 30 W/m 65 °C 80 °C 140 m K30A100 100 m 30 W/m 65 °C 80 °C 140 m K40A25 25 m 40 W/m 65 °C 80 °C 120 m K40A50 50 m 40 W/m 65 °C 80 °C 120 m K40A100 100 m 40 W/m 65 °C 80 °C 120 m -
HOMOLOGATION AND INSTALLATION
Homologation
- CSTB
- CE
Installation and use- The cable can be cut to the desired length;
- The total power depends on the length of the heating cable and the perceived temperature;
- The cable is secured along the pipe with the relevant fixing tape K50 for steel pipes or K50AL for plastic pipes;
- Minimum bending radius: 25 mm;
- Use a C01A, C03A or L03BM1A type thermostat to disconnect the heating cable when the temperature of the fluid is at the desired temperature, thereby minimising energy consumption;
- The cable heats up along its entire length and can be wound in overlapping spirals as it will limit its power at the overlapping points;
- The two conductors must be kept insulated at the end of the cable using the kit to seal the ends code KIT2A and must never be in contact with each other;
- It is advisable to apply an insulating coating over the heating cable.
- The heating cables automatically vary the heat emission without control thermostats being used;
- They consist of conductors insulated by polymers, which vary their resistance according to the temperature which they are subjected to.