Antifreeze heating cables with constant power for road ramps
-
DESCRIPTION
General features0
Suitable for laying under access ramps, parking lots, pavements and walkways.
Constant power delivered ~17 W/m.
They require control thermostats to be used.
- Cable composition:
– 2 conductors in solid copper and tinned copper
– Outer sheath in pvc
– Aluminium foil shielding
– Tinned copper sheath - The heating cable includes:
– 1 standard length of heating cable
– 2 cold tails - Minimum installation room temperature 5 °C
- Maximum room temperature 65 °C
- Minimum storage room temperature -20 ÷ -25°C
Electric features- Power supply 230V-50Hz
- Constant power delivered ~17W/m
- Total power absorbed at 230V:
– K17C29 510 W
– K17C73 1260 W
– K17C82 1530 W
– K17C102 1750 W
– K17C129 2200 W
- Cable composition:
-
ADVANTAGES
0
Suitable for laying under access ramps, parking lots, pavements and walkways.
Constant power delivered ~17 W/m.
They require control thermostats to be used.
Advantages -
TECHNICAL SPECIFICATION
CODE CABLE LENGTH TOTAL POWER ABSORBED AT 230V HEATED SURFACE WITH 130W/M MINIMUM INSTALLATION ROOM TEMPERATURE MAXIMUM ROOM TEMPERATURE K17C29 30.42 m 510 W 3 m² 5 °C 65 °C K17C73 74.28 m 1260 W 6 m² 5 °C 65 °C K17C82 89.34 m 1530 W 7 m² 5 °C 65 °C K17C102 101.98 m 1750 W 9 m² 5 °C 65 °C K17C129 124.58 m 2200 W 11 m² 5 °C 65 °C -
HOMOLOGATION AND INSTALLATION
Homologation
- CE
Installation and use- The two ends of the cable must be connected to the phase and to the neutral in a special junction box;
- Along its path, the cable must not overlap and the original length must not be cut;
- It is recommended to use a sturdy flexible sheath to protect the terminals and cold tails and for the branches to be easily inspected after installation;
- The cable will be laid at a depth of 50 mm in a bed of sand and cement with a serpentine path with a 100 mm pitch, therefore it is advisable to form a path by securing the cable with KJSSP spacing bars;
- It is advisable to apply an insulating coating over the heating cable for a correct installation.
- The heating cables consist of a coil-wound resistance on two conductors. The resistance is in contact with the conductors through splicing points at constant intervals; the energy to heat the resistance is drawn at the splicing points;
- The heating cables are supplied in reels of standard length that cannot be cut or stretched;
- They require L03BM1A type control thermostats.
ACCESSORIES
- Code KBE3A: junction box in insulating material;
- Code KSUPP-A: support foot for the KBE3A junction box;
- Code KJSSP: spacing bars;
- Code L03BM1A: ON/OFF thermostat – proportional – P.I.D. at 1 outlet;
- Code L04BM2A: ON/OFF thermostat, 2 outputs, wall-mounting;
- Code L23EM1A: ON/OFF humidistat DIN rail mounting.
- Code L24EM2: humidistat, wall-mounting
- Code LS160A: probe for humidistat L23EM1A
- TECHNICAL LITERATURE
-
FAQS