Gas detection sensors for control units P30A and P70
-
DESCRIPTION
General features0
Combustible gas detection sensors to be used with the electronic control units P30A and P70. The sensors are available in 2 versions: S71 for methane gas and city gas, S72 for LPG.
Electric features- Casing in shockproof insulating material.
- Green LED to indicate power supply.
- Red LED to indicate triggering.
- Orange LED to indicate sensor failure.
- Positive safety connections with the detector (the control unit detects an error, in case of incorrect connections or interruption of the connection).
- Unit weight 0,18 Kg.
-
ADVANTAGES
0
Combustible gas detection sensors to be used with the electronic control units P30A and P70. The sensors are available in 2 versions: S71 for methane gas and city gas, S72 for LPG.
Advantages -
TECHNICAL SPECIFICATION
Gas typeOperating ambienttemperatureProtectiondegreeS71
Methane gas or other light gas
– 10 ÷ 50°C
IP54S72LPG gas (cylinder liquid gas) or other heavy gas
– 10 ÷ 50°C
IP54 -
HOMOLOGATION AND INSTALLATION
Homologation
- Complies with EN 60730-1 standards.
Installation and useWall mounting.
Detection sensors should be fixed on the wall at a distance of approximately 2 meters from the gas using device in such position in order to allow natural air circulation:
– S71 for specific light gases (methane gas, city gas), this sensor has to be installed at a high level approximately 30-40 cm from the ceiling.
– S72 for heavy gases (cylinder liquid gas LPG), this sensor has to be installed to a low level approximately 30-40 cm above the floor.Avoid installing the sensors:
– behind barriers that hinder the air natural circulation in the environment.
– near vents (keeping a minimum distance of 2 meters).
– away from steam, smoke and other fumes.Remove the cover by unscrewing the four front screws.
Install the base on the wall using for the cable input the appropriate cable gland.- The intervention threshold of the sensors is adjusted in the factory to a value that allows the signaling of gas presence at a concentration much lower than the danger limits.
- The sensors are provided with an intervention light signaling and the connections with the control unit have positive safety (their disconnection causes the detector intervention).