Suitable for signalling, controlling and regulating the air flow in air conditioning systems; to control fans, compressors, etc.
General features
Case in shock-proof plastic with self-retaining screws
AISI 301 stainless steel flexible blade (50 x 165 mm)
Electric connections on Faston 6.3 (provided)
Calibration screw for adjusting the cut-in point
PVC flange, 5 mm thick
Compliance with standards CEI EN 60730-1.
SPDT single-pole switching microswitch
Electric features
Rated insulation voltage Ui 380V~
Continuous duty rated current Ith 10A
ADVANTAGES
0
Suitable for signalling, controlling and regulating the air flow in air conditioning systems; to control fans, compressors, etc.
Advantages
TECHNICAL SPECIFICATION
CODE
MIN DISENGAGE
VALUE (C-NO opens,
C-NC closes)
MIN ENGAGE
VALUE (C-NC opens,
C-NO CLOSES)
MAX DISENGAGE
VALUE (C-NO opens,
C-NC CLOSES)
MAX ENGAGE
VALUE (C-NC opens,
C-NO closes)
FF71A
2.5 m/sec
3.1 m/sec
6.4 m/sec
7 m/sec
HOMOLOGATION AND INSTALLATION
Homologation
Complies with CEI EN 60947-5-1 standards
Installation and use
Whenever possible, the air flow switches should be installed on a horizontal part of the piping or ducting.
A flexible blade, of appropriate dimensions, is activated by the air flow, determining an angular displacement of a rod that, mechanically connected to a fluctuating arm, actuates an electric SPDT switch.
Avoid therefore to place it where air currents are too strong, as well as near bends, fans or at any point where excessive turbulence may occur.
The arrow on the cover must correspond to the direction of the air flow.