Pressure switches up to 300 bar with adjustable differential
-
DESCRIPTION
General features0
Pressure switches for control and regulation of all fluids and non-explosive gases.
Suitable for compression plants, boilers, tanks, autoclaves, ventilation plants, lubrication plants and in general whenever a pressure up to 300 bar must be controlled.
- Piston sensitive element, brass connection.
- Metallic frame.
- Cover in shockproof thermoplastic material.
- Output connections with PVC cable gland.
- Adjustable differential.
- Male connection G 1/4.
- Maximum temperature of the controlled fluid: 80°C.
- Pressure switch body admissible temperature: 60°C.
- Storage and transport temperature: -35 ÷ 60°C.
- Unit weight: 0,47 Kg B12FN-B12GN.
- Unit weight: 0,46 Kg B12HN.
ACCESSORIES
- G1/2 cable gland in V0 self-extinguishing, shockproof thermoplastic material, code: 303298LA
- IP44 protection casing IP44, code: 2593367
Electric features- Rated insulation voltage Ui 415V~
- Continuous duty rated current Ith 16A
-
ADVANTAGES
0
Pressure switches for control and regulation of all fluids and non-explosive gases.
Suitable for compression plants, boilers, tanks, autoclaves, ventilation plants, lubrication plants and in general whenever a pressure up to 300 bar must be controlled.
Advantages -
TECHNICAL SPECIFICATION
CODE RESET RANGE DIFFERENTIAL SENSITIVE
ELEMENT
MAX. PRESSURECONNECTION G 1/4
PROTECTION
DEGREEB12FN automatic 12 ÷ 50 bar 6 ÷ 15 bar 60 bar male IP40 B12GN automatic 25 ÷ 150 bar 12 ÷ 40 bar 180 bar male IP40 B12HN automatic 60 ÷ 300 bar 40 ÷ 80 bar 350 bar male IP40 B12FMN * manual 12 ÷ 50 bar 6 ÷ 15 bar 60 bar male IP40 B12GMN * manual 25 ÷ 150 bar 12 ÷ 40 bar 180 bar male IP40 B12HMN * manual 60 ÷ 300 bar 40 ÷ 80 bar 350 bar male IP40 B12FNY automatic 12 ÷ 50 bar 6 ÷ 15 bar 60 bar male IP65 B12GNY automatic 25 ÷ 150 bar 12 ÷ 40 bar 180 bar male IP65 B12HNY automatic 60 ÷ 300 bar 40 ÷ 80 bar 350 bar male IP65 * delivery time and minimum purchase quantity upon request 1 Bar = 100Kpa The differential must be deducted from the range value -
HOMOLOGATION AND INSTALLATION
Homologation
- Complies with CE 0497 Directives.
- Complies with EN 60947-1 and 60947-5-1 standards.
Installation and use- Direct installation on the pipe.
- If these devices are used as control pressostats (pressure lack), verify that maximum pressure does not exceed maximum supported sensitive element pressure.
- Possibility of mounting on metallic clamp, exept for the waterproof casing versions.
- When pressure increases: 1-2 opens, 1-4 closes.
- In case of fluid temperatures higher than the maximum allowed, connect the pressure switch to the pipe by inserting a metallic spiral between the pressure switch and the pipe to facilitate heat dispersion.
- In the pressure switch with blocking and manual reset at maximum pressure, the reset takes place when the pressure is below the
value set on differential.
- TECHNICAL LITERATURE
-
FAQS